Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM06275
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/26/2008 | ELECTRIC - INTERMEDIATE | Approved | SERVICE KILL-SAT 1/26/08 CONTRACTOR REQUEST AFTER HOURS INSPECTION $150 PAID WITH CHECK #88328 |
|
01/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/22/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
01/18/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK ABOVE CEILING ROOMS #132, 134, 137, 133, 136 - BONDING OF 480V DISC. SWITCHES ON ROOF TO MEET THE REQUIREMENTS OF 250.97 |
|
01/11/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK ABOVE CEILINGS IN ROOMS 106, 105, FITNESS ROOM 104, 111, 113, 117, 116, 118 - OK ELECTRIC ROOM, PANEL MAKE UP IN #229 AND PANELS L2, L3 (NICE WORK ON PANEL MAKE UP) |
|
01/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK GROUNDING FOR SES 2) DISREGARD NOTE FOR GFI PROTECTION LAST INSPECTION 3) OK TO CLEAR TEMP POWER (TEC FOR #2M)-NO BOND REQUIRED 4) RECEIVED LETTER OF TORQUE FOR SES |
|
01/04/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK SECURITY & LIGHT POLE FOOD CONDUITS AT NORTH NORTHEAST OUTSIDE OF BLD. - SERVICE IS 277-480V 3/0 1200 AMP. MUST COMPLY WITH 230.95 NEC FOR GROUND FAULT REQUIREMENTS |
|
11/21/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
11/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* SUPPORT MC PER NEC -- WITHIN 12" AT TERM. AND AT 6' INTERVALS |
|
11/08/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ROUGH PROCESSING AREA CONTACT #955-0202 (CELL) JOSH BECK |
|
11/01/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SOUTH EXTERIOR (WEST) WALLS OK SOUTH ENTRANCE TO COLUMN "C" WALLS |
|
10/24/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK NORTH OF COLUMN "C" AND EAST OF GRID LINE #4 - CHECK MAKE UP PRIOR TO INSTALLING DEVICES |
|
10/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS #125 |
|
09/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS ADMIN. OFFICES UPPER LEVEL |