Permit: T06CM06275

Parcel: 132166460


Addresses:

945 E OHIO ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM06275

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
01/26/2008 ELECTRIC - INTERMEDIATE Approved SERVICE KILL-SAT 1/26/08
CONTRACTOR REQUEST AFTER HOURS INSPECTION $150 PAID WITH CHECK #88328
01/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/22/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
01/18/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK ABOVE CEILING ROOMS #132, 134, 137, 133, 136
- BONDING OF 480V DISC. SWITCHES ON ROOF TO MEET THE REQUIREMENTS OF 250.97
01/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK ABOVE CEILINGS IN ROOMS 106, 105, FITNESS ROOM 104, 111, 113, 117, 116, 118
- OK ELECTRIC ROOM, PANEL MAKE UP IN #229 AND
PANELS L2, L3 (NICE WORK ON PANEL MAKE UP)
01/08/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK GROUNDING FOR SES
2) DISREGARD NOTE FOR GFI PROTECTION LAST INSPECTION
3) OK TO CLEAR TEMP POWER (TEC FOR #2M)-NO BOND REQUIRED
4) RECEIVED LETTER OF TORQUE FOR SES
01/04/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK SECURITY & LIGHT POLE FOOD CONDUITS AT NORTH
NORTHEAST OUTSIDE OF BLD.
- SERVICE IS 277-480V 3/0 1200 AMP. MUST COMPLY
WITH 230.95 NEC FOR GROUND FAULT REQUIREMENTS
11/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
11/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
SUPPORT MC PER NEC -- WITHIN 12" AT TERM. AND AT 6' INTERVALS
11/08/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ROUGH PROCESSING AREA
CONTACT #955-0202 (CELL) JOSH BECK
11/01/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SOUTH EXTERIOR (WEST) WALLS
OK SOUTH ENTRANCE TO COLUMN "C" WALLS
10/24/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK NORTH OF COLUMN "C" AND EAST OF GRID LINE #4
- CHECK MAKE UP PRIOR TO INSTALLING DEVICES
10/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS #125
09/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS ADMIN. OFFICES UPPER LEVEL