Permit: T06CM06275

Parcel: 132166460


Addresses:

945 E OHIO ST


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06CM06275

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
03/11/2008 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
01/25/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
- OK LIGHTING GROUNDING ARRAY AT SOUTH OUTSIDE BLD.
- OK PANEL, MAKE UP AT N4, EP3, EL3, L-2,
- FOR ABOVE CEILING TO BE APPROVED ALL DATA, COMM, SECURITY WIRING MUST BE COMPLETE, BOXES COVERED.
01/22/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
01/09/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 4 POLE BASES N.E OF BLD
01/04/2008 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
12/21/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
12/03/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 4" FROM BLD. TO SECURITY GATES ON NORTH & EAST SIDES OF BLD OUTSIDE & POWER FOR GATES & POLE LTG.
09/17/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 4" & 3 POWER FROM COMM/ROOM TO RAMP AT S.E CORNER EXTERIOR OF BLDG.
08/06/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK U.G BELOW SLAB DATA/PHONE ROOM AREA
07/25/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/12/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK UNDER SLAB CONDUITS FOR FLOOR BOXES
ROOM #200. OK 4" COMM. CONDUITS FROM ROOM #157 TO SOUTH EXT. BLD. WALL ALSO, 3/0 GROUND TO SOME LOCATIONS
07/11/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
07/06/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
1. 4 - 2" PVC'S - CONDUITS
FROM SERVICE INSIDE
2. 2 - 1" PVC'S - CONDUITS
FROM SERVICE INSIDE

BOTH RUNS TO COMMUNICATIONS ROOM

2. 5 - 4" PVC'S FROM O/S TEP TRANSFORMER TO INSIDE SES