Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM06275
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* 1) WAITING FOR E-MAIL ONLY |
|
05/19/2008 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* ELEC. AND FIRE FINALS APPROVED APPROVED PENDING APPEALED ITEMS #2 & #3 |
|
05/12/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
04/25/2008 | BUILDING - FINAL | Partial Approval | #2 FROM 4-3-08 UNDER APPEAL #3 FROM 4-3-08 FRONT SIDEWALK IS DONE BUT NOT REAR #10 FROM 4-3-08 HAS NOT BEEN DONE. FIRE SPRINKLER FINAL NEEDED ELECTRICAL FINAL NEEDED |
|
04/03/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. POST 15" ADDRESS DISPLAY REQUIRED 2. PROVIDE ACCESSIBLE ROUTE FROM PUBLIC WAY 3. PROVIDE DETECTABLE WARNINGS AT WALKS ADJACENT TO VEHICULAR AREAS PER ADAAG 4.29.5 4. MAXIMUM PULL ON DOORS TO BE 5 LBS. (4.13.11) 5. PROVIDE 27"? KNEE CLEARANCE @ BREAKROOM SINK OTHER SINKS OK FOR PARALLEL APPROVALS 6. CLEARANCE AT LATCH SIDE OF UPPER LEVEL WOMENS STALL DOOR TO BE 18" MIN. 7. PUT MESH IN @ GUARD BY DOCK 8. 2% MAX. SLOPE @ H.C PARKING CARPORT SOUTH 9. GET RESTROOM SIGNAGE MOUNTED IN PROPER LOCATION 10. DETECTABLE CANE WARNING REQUIRED AT DRINK FOUNTAIN PUBLIC LOBBY |