Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
Permit Number - T06CM06274
Inspection Description - ELECTRIC - TEMP POWER FOR TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/02/2007 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
10/29/2007 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* | |
10/11/2007 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1) UL AND CSA NUMBERS DO NOT MATCH PRODUCT PARK NUMBERS |
|
10/09/2007 | ELECTRIC - TEMP POWER FOR TEST | Partial Approval | IVRS - Inspection :* 1. BOND NIPPLE TO 400 AMP DISCONNECT 250.92 2. FINISH #2, 3, 4, 5, 9 & 13 |
|
09/10/2007 | ELECTRIC - TEMP POWER FOR TEST | Not ready for Inspection | IVRS - Inspection :* 1. SERVICES TO BE GROUNDED PER CITY AMENDMENT 2. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE TO GROUNDED CONDUCTOR ALSO ACCESSIBLE 3. IDENTIFY GROUNDING CONDUCTORS 250.119 4. BONDING JUMPERS TO BE SIZED PER 250.102 & 250.66 5. HUBS TO BE LISTED FOR BONDING PER 250.92 ALSO, BONDING DEVICES ON HUBS PER 250.92 6. BOND CT ENCLOSURE (LEFT) 7. PLEASE VERIFY GUTTER FILL 8. MAINTAIN WIRE BENDING RADIUS 9. INSTALL CONDUCTORS THROUGH NIPPLES GROUPED A-B-C AND NEUTRAL 300.3 10. DO NOT MODIFY MULTI-TAP FROM LISTING 11. VERIFY GROUNDING ELECTRODE CONDUCTOR 12. TERMINATE ALL CIRCUITS - PLUG OR PLATE ALL DEVICES 8' AND BELOW 13. INSTALL ARC FLASH LABELING 14. WIRE SIZES NOT AS PER PLANS |