Permit: T06CM06274

Parcel: 12703559B


Addresses:

5515 E 5TH ST #109


Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Permit Number - T06CM06274

Inspection Description - ELECTRIC - TEMP POWER FOR TEST

Inspection Status - Approved

Date Description Inspector Results Comments
11/02/2007 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
10/29/2007 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
10/11/2007 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1) UL AND CSA NUMBERS DO NOT MATCH PRODUCT PARK NUMBERS
10/09/2007 ELECTRIC - TEMP POWER FOR TEST Partial Approval IVRS - Inspection :*
1. BOND NIPPLE TO 400 AMP DISCONNECT 250.92
2. FINISH #2, 3, 4, 5, 9 & 13
09/10/2007 ELECTRIC - TEMP POWER FOR TEST Not ready for Inspection IVRS - Inspection :*
1. SERVICES TO BE GROUNDED PER CITY AMENDMENT
2. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE TO GROUNDED CONDUCTOR ALSO ACCESSIBLE
3. IDENTIFY GROUNDING CONDUCTORS 250.119
4. BONDING JUMPERS TO BE SIZED PER 250.102 & 250.66
5. HUBS TO BE LISTED FOR BONDING PER 250.92
ALSO, BONDING DEVICES ON HUBS PER 250.92
6. BOND CT ENCLOSURE (LEFT)
7. PLEASE VERIFY GUTTER FILL
8. MAINTAIN WIRE BENDING RADIUS
9. INSTALL CONDUCTORS THROUGH NIPPLES GROUPED A-B-C AND NEUTRAL 300.3
10. DO NOT MODIFY MULTI-TAP FROM LISTING
11. VERIFY GROUNDING ELECTRODE CONDUCTOR
12. TERMINATE ALL CIRCUITS - PLUG OR PLATE ALL DEVICES 8' AND BELOW
13. INSTALL ARC FLASH LABELING
14. WIRE SIZES NOT AS PER PLANS