Permit: T06CM06272

Parcel: 13623007Y

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM06272

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/12/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
07/11/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
07/09/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. INSTALL ALL BACKFLOW DEVICES PER PLAN AND AS REQUIRED FOR APPLIANCES WITH DIRECT WATER CONNECTION THAT ARE NOT LISTED OR HAVE PROOF OF 1" AIR GAP.
2. PROVIDE MINIMUM FALL ON 3" 3-COMP SINK GREASE
DRAIN PIPE
3. ALL CLEANOUTS TO HAVE FACTORY TAPPED PLUGS & MACHINE SCREWS FOR CLEANOUT COVERS.
4. ALL APPLIANCES TO BE INSTALLED
5. PROVIDE BACKFLOW CERTIFICATIONS
6. INSTALL HEAT TRAPS FOR WATER HEATER PER PLAN AND INSULATE 8' INLET & 8' OUTLET PIPING OF WATER HEATER PIPING PER 2003 ENERGY CONSERVATION CODE
7. VENTS THRU ROOF TO BE LATEX PAINTED FOR SUN EXPOSURE.
8. PROVIDE TRAFFIC RATED CLEANOUT COVER FOR TRAFFIC AREA