Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T06CM06272
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/09/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* REVISED APPROVED PLAN ON SITE |
|
07/06/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. 4" ABS TO HCS TIE IN OK REMOVE 2" THREADED TEST TEE UNDERGROUND 2. OK TO COVER 4" |
|
07/05/2007 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
05/21/2007 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* 1. FROM BUILDING EXTERIOR SANITARY STUB OUT 4" BACK THRU BUILDING WASTE & VENT THRU ROOF (WATER TEST) 2. 4" CLEANOUTS FOR UPPER TERMINAL AT BOTH STOOLS TO BE ACCESSIBLE WITHOUT STOOL REMOVAL. 3. 3" GREASE WASTE STUB FROM BUILDING EXTERIOR BACK THRU BUILDING THRU ROOF WITH 2" GREASE TRAP VENT OK. 4. GREASE TRAP AND SANITARY DRAINAGE TO BE REVISED AND SHOWN ON CITY APPROVED PLAN. WATER PIPING IN WALL OK. 5. OVERHEAD WATER TO BE INSTALLED PER PLAN FOR SIZING AND VALVE REQUIREMENTS. |
|
05/16/2007 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SHALL HAVE A CITY APPROVED PLAN ON SITE AT TIME OF INSPECTION. HAVE APPROVED HEALTH DEPT ON SITE. |