Permit: T06CM06272

Parcel: 13623007Y

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM06272

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
07/09/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
REVISED APPROVED PLAN ON SITE
07/06/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. 4" ABS TO HCS TIE IN OK REMOVE 2" THREADED
TEST TEE UNDERGROUND
2. OK TO COVER 4"
07/05/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
CANCELLED
05/21/2007 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
1. FROM BUILDING EXTERIOR SANITARY STUB OUT 4" BACK THRU BUILDING WASTE & VENT THRU ROOF (WATER TEST)
2. 4" CLEANOUTS FOR UPPER TERMINAL AT BOTH STOOLS TO BE ACCESSIBLE WITHOUT STOOL REMOVAL.
3. 3" GREASE WASTE STUB FROM BUILDING EXTERIOR BACK THRU BUILDING THRU ROOF WITH 2" GREASE TRAP VENT OK.
4. GREASE TRAP AND SANITARY DRAINAGE TO BE REVISED AND SHOWN ON CITY APPROVED PLAN. WATER PIPING IN WALL OK.
5. OVERHEAD WATER TO BE INSTALLED PER PLAN FOR SIZING AND VALVE REQUIREMENTS.
05/16/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SHALL HAVE A CITY APPROVED PLAN ON SITE AT TIME OF INSPECTION. HAVE APPROVED HEALTH DEPT ON SITE.