Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RECEPTACLES TO BE TIGHTENED SECURELY TO WALL, CHECK ALL. NEC 406.4 2. HVAC UNIT #2 OVERFUSED. MAX 35 AMP 3. INSTALL SERVICE RECEPTACLE WITHIN 25' OF AC & REFRIGERATION EQUIPMENT -- NEC 210.63 4. INSTALL DISCONNECT SWITCHES FOR BLOWER UNITS IN WALK-IN COOLER & FREEZER -- NEC 430.102 5. CANNOT INSTALL OVERCURRENT PROTECTION ON NEUTRAL CONDUCTOR CHECK CONDENSING UNIT ON ROOFTOP FOR WALK-IN --- NEC 240.22 6. HAVE APPROVED SET OF DRAWINGS ON JOB SITE MISSING E-1.2 7. RECALL WHEN READY |