Permit: T06CM06272

Parcel: 13623007Y

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06272

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/11/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. RECEPTACLES TO BE TIGHTENED SECURELY TO WALL, CHECK ALL. NEC 406.4
2. HVAC UNIT #2 OVERFUSED. MAX 35 AMP
3. INSTALL SERVICE RECEPTACLE WITHIN 25' OF AC & REFRIGERATION EQUIPMENT -- NEC 210.63
4. INSTALL DISCONNECT SWITCHES FOR BLOWER UNITS IN WALK-IN COOLER & FREEZER -- NEC 430.102
5. CANNOT INSTALL OVERCURRENT PROTECTION ON NEUTRAL CONDUCTOR CHECK CONDENSING UNIT ON ROOFTOP FOR WALK-IN --- NEC 240.22
6. HAVE APPROVED SET OF DRAWINGS ON JOB SITE
MISSING E-1.2
7. RECALL WHEN READY