Permit: T06CM06270

Parcel: 136238620

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06270

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/05/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DO NOT HAVE PROPER/SAFE WORKING CLEARANCE IN FRONT OF PANEL AT EQUIPMENT - NEC 110.26
2. CONNECT GROUNDING CONDUCTOR TO JUNCTION BOX
10" X 10" HAVE SPLICES IN BOX - NEC 250.148