Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/30/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 11/27/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) CALL BACK FOR CLOSET FLANGE INSPECTION |
|
| 10/17/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/05/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ALL EXTERIOR WORK TO BE COMPLETED OR APPROVED PLAN TO BE REVISED. NOTE: HANIDCAP STOOL TO BE 16" TO 18" FROM FINISH SIDE WALL. WATER TEST WASTE & VENT RESTROOM ONLY FROM 3" EXTERIOR 2-WAY THRU ROOF. WATER DISTRIBUTION RESTROOM ONLY. SHALL RECALL 03005 FOR PIPE WRAPS PRIOR TO CONCRETE. APPROVED PLAN SHALL REFLECT WORK ON SITE FOR CONTINUOUS TRENCH DRAINAGE THRU ENTIRE BUILDING INSTA-HOT WATER HEATER TO BE SHOWN IN PLACE OF TANK TYPE WATER HEATER ON PLAN. OVERHEAD PIPING TO BE PROPERLY SUPPORTED. |
|
| 09/28/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SHALL PROVIDE TEST ON ALL PIPING AT TIME OF INSPECTION 2. SHALL PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR ALL DRAINAGE 3. SHALL PROVIDE APPROVED WATER PIPING (PVC IS NOT) 4. SHALL PROVIDE CORRECT DRAINAGE FOR DRINKING FOUNTAIN, YOU CANNOT DUMP DRAIN INTO VENT OF STOOL INSTALL PER APPROVED PLAN OR PROVIDE REDLINE ON SITE AT TIME OF INSPECTION WITH REVISED APPROVED PLAN TO FOLLOW 5. OVERHEAD HORIZONTAL VENT PIPING TO BE SUPPORTED AT 4' INTERVALS AND CHANGES OF ELEVATION & DIRECTION LIST NOT COMPLETE |