Permit: T06CM06267

Parcel: 12009052A


Addresses:

4415 S 6TH AV

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
11/30/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
11/27/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CALL BACK FOR CLOSET FLANGE INSPECTION
10/17/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
10/05/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ALL EXTERIOR WORK TO BE COMPLETED OR APPROVED PLAN TO BE REVISED.

NOTE: HANIDCAP STOOL TO BE 16" TO 18" FROM FINISH SIDE WALL.
WATER TEST WASTE & VENT RESTROOM ONLY FROM 3" EXTERIOR 2-WAY THRU ROOF. WATER DISTRIBUTION RESTROOM ONLY. SHALL RECALL 03005 FOR PIPE WRAPS PRIOR TO CONCRETE. APPROVED PLAN SHALL REFLECT WORK ON SITE FOR CONTINUOUS TRENCH DRAINAGE THRU ENTIRE BUILDING INSTA-HOT WATER HEATER TO BE SHOWN IN PLACE OF TANK TYPE WATER HEATER ON PLAN. OVERHEAD PIPING TO BE PROPERLY SUPPORTED.
09/28/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE TEST ON ALL PIPING AT TIME OF INSPECTION
2. SHALL PROVIDE LONG RADIUS DRAINAGE FITTINGS FOR ALL DRAINAGE
3. SHALL PROVIDE APPROVED WATER PIPING (PVC IS NOT)
4. SHALL PROVIDE CORRECT DRAINAGE FOR DRINKING FOUNTAIN, YOU CANNOT DUMP DRAIN INTO VENT OF STOOL
INSTALL PER APPROVED PLAN OR PROVIDE REDLINE ON SITE AT TIME OF INSPECTION WITH REVISED APPROVED PLAN TO FOLLOW
5. OVERHEAD HORIZONTAL VENT PIPING TO BE SUPPORTED
AT 4' INTERVALS AND CHANGES OF ELEVATION & DIRECTION

LIST NOT COMPLETE