Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/09/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/06/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BLD. LOCKED, NO MESSAGE |
|
| 01/29/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ITEM #2 ON LETTER FROM ROLDAN (PE) NOT CORRECTED 2. NEW #2 GROUND TO TERMINATE ON GROUND BAR IN GUTTER NOT NEUTRAL BAR |
|
| 12/17/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. #2 GROUND ELECTRODE CONDUCTOR IS EXISTING AT SERVICE, OK PER CODE, HOWEVER, PLANS SHOW A 4/0 WIRE 2. CU #1 TO BE DELETED, CRC#1 NOT INSTALLED AT THIS TIME 3. PLAN SHOWS 1/0 GROUND RUN TO INSIDE GUTTER FROM SERVICE DISCONNECT |
|
| 12/16/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 01/30/2008 | ELECTRIC - FINAL | Denied | PREVIOUS APPROVAL ON 1/25/08 BY DSANTACRUZ WAS IN ERROR AND HAS BEEN DELETED. IT WAS IMPROPER FOR CONTRACTOR TO KNOWINGLY SUBMIT PLANS TO MR. SANTACRUZ THAT HAD NOT BEEN APPROVED BY THE CITY,NOR THE ARCHITECT. |