Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM06265
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/15/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
03/14/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CALL IN 03035 & 03090 AFTER COMPLETION OF ALL ITEMS 1. ALL OVERHEAD PIPING TO BE SUPPORTED AT CORRECT INTERVALS WITH APPROVED METHODS. 2. PROVIDE CORRECT FITTINGS & COUPLINGS FOR VENT CONNECTION TO EXISTING, EXISTING IS PVC SCH40 PROVIDE PVC SCH 40 AT THIS LOCATION WITH CORRECT TRANSITION COUPLING TO ABS (MISSION STYLE SHIELDED) 3. PROVIDE EXPANSION TANK FOR WATER HEATER CORRECTLY SUPPORTED. 4. PROVIDE FACTORY TAPPED CLEANOUT PLUGS WITH CLEANOUT COVERS AND MACHINE SCREWS FOR CLEANOUTS. 5. ALL FIXTURES TO BE MADE WATER TIGHT AT WALLS & FLOOR SURFACES. 6. PIPING FOR T&P AND WATER HEATER PAN TO BE PROPERLY SECURED AND HAVE 1" AIR GAP AT MOP SINK. 7. INSTALL WATER HEATER PER PIPING DIAGRAM (1) ON P3.0 8. WATER HEATER PIPING TO BE INSULATED PER 2003 ECC 1ST 8' IN ON COLD & 8' OUT ON HOT. 9. YOUR MOP SINK DOES NOT MEET PLAN SPEC. AS DISCUSSED AT ROUGH SOIL. INSTALL PER PLAN OR PROVIDE STAMPED LETTER FORM ENGINEER GIVING OK FOR ALTERNATE. FAILURE TO COMPLY WILL RESULT IN REFEE |