Permit: T06CM06265

Parcel: 136406740


Addresses:

9660 E 22ND ST #180


Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T06CM06265

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
03/08/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
WATER TEST WASTE & VENT TO POINT OF CONNECTION OK
03/06/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
(NO CALL BACK PHONE NUMBER ON MESSAGE)
1. SHALL PROVIDE CORRECT MISSION STYLE TRANSITION COUPLING AT COMBO CONNECTION TO MAIN.
2. INSTALL DRAINAGE PER PLAN, 3" MOP SINK IS IN FIXTURE SCHEDULE. THIS FIXTURE ON SITE DOES NOT MEET SCHEDULE REQUIREMENT.
3. TEST WASTE & VENT PIPING TO POINT OF CONNECTION AT VENT.
4. PROVIDE PIPE WRAPS AT PIPE PENETRATIONS THRU CONCRETE AREA OF FLOOR.
02/28/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE CORRECT PLASTIC X PLASTIC COUPLINGS AT EXISTING.
2. SHALL INSTALL PER APPROVED PLAN ALL PIPING
3. SHALL HAVE TEST ON WASTE & VENT THRU ROOF & WATER PIPING