Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T06CM06265
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/08/2007 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* WATER TEST WASTE & VENT TO POINT OF CONNECTION OK |
|
03/06/2007 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* (NO CALL BACK PHONE NUMBER ON MESSAGE) 1. SHALL PROVIDE CORRECT MISSION STYLE TRANSITION COUPLING AT COMBO CONNECTION TO MAIN. 2. INSTALL DRAINAGE PER PLAN, 3" MOP SINK IS IN FIXTURE SCHEDULE. THIS FIXTURE ON SITE DOES NOT MEET SCHEDULE REQUIREMENT. 3. TEST WASTE & VENT PIPING TO POINT OF CONNECTION AT VENT. 4. PROVIDE PIPE WRAPS AT PIPE PENETRATIONS THRU CONCRETE AREA OF FLOOR. |
|
02/28/2007 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SHALL PROVIDE CORRECT PLASTIC X PLASTIC COUPLINGS AT EXISTING. 2. SHALL INSTALL PER APPROVED PLAN ALL PIPING 3. SHALL HAVE TEST ON WASTE & VENT THRU ROOF & WATER PIPING |