Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM06262
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/05/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 03/02/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) COMPLETE #6 OF PREVIOUS INSPECTION ON 2/26/07 2) NEED ONE STRAP AT FRONT 3) NAIL ALL STUDS VERTICALLY AT H.D.'S |
|
| 02/26/2007 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) MISSING WIND BRACE 2ND FLOOR WEST REAR 2) WEB STIFFNERS AT TJI'S, FOLLOW SHEAR TRANSFER DETAIL 3) CMST 16 STRAPS ARE 3" WIDE X 22 NAILS TOP AND BOTTOM 4) HANGERS ON TOP CHORD AT PORCH HIPS 5) FLOOR TRUSS HANGER NEAR STAIR 6) USE SCHEDULE TO TIE SHEARWALLS TO TRUSS TOP CHORD |
|
| 02/22/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ALL HOLDOWNS NEED TO BE EPOXIED 2) MISSING COIL STRAP ON EAST WALL 3) MISSING H2.5 ON BEARING WALL PER 7/DT2 GARAGE HALLWAY 4) HANGERS UNDER ARCH WAY MISSING NAILS 5) MISSING BLOCKING ON PERIMETER FLOOR JOIST PER 6/DT2 6) H.D. 2ND FLOOR NOT NAILED 7) NO ACCESS TO ROOF |
|
| 02/20/2007 | EXT METAL CLIPS/EXT SHEATHING | Denied | CMST 16 NEEDED ON 2ND FLOOR ABOVE DINING |