Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2007 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 01/23/2007 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE PAGE S-1 2) FOOTINGS NEED TO BE 19" WIDE 3) ALTERNATE VERTS AND SUPPORT VERTICAL REBAR PRIOR TO POUR 4) VERTICAL REBAR TO BE 48" ON CENTER AND EACH SIDE OF EVERY OPENING |