Permit: T06CM06241

Parcel: 140180280

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Date Description Inspector Results Comments
07/30/2007 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
1. INSTALL SPLIT BOLT TO CONNECT #4 BARE FOR EACH SERVICE TOGETHER
2. STRAP #4 TO WALL
3. RISER STRAPS ARE PULLED OUT OF WALL
4. PLANS NOT ON SITE
07/26/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. THE RISER COMING UP INTO SERVICE #1 IS INSTALLED IMPROPERLY - COMES INTO BOTTOM OF SERVICE AT AN ANGLE AS TO WHERE IT PULLS DOWN BOTTOM OF SERVICE
2. BOTH HUBS AT BOTTOM OF SERVICES INCORRECTLY INSTALLED
3. USE ROMEX CONNECTORS WHERE GROUNDS ENTER AT BOTTOM OF SERVICES
4. DOORS LOCKED - NEED TO SEE INTERIOR
TO SEE IF READY
5. BOTTOM OF RISERS TO HAVE MORE DIRT COVERAGE
07/25/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/31/2007 ELECTRIC - TEMPORARY SERVICE Not ready for Inspection IVRS - Inspection :*