Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM06240
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/29/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSTALL K.O. BLANKS IN BOXES AS NEEDED-NEC 314.17 2) SCREWS NOT ALLOWED ON INTERIOR OF BOXES FOR MOUNTING NEC 314.23 B1 3) OK TO COVER WALLS AFTER CORRECTIONS 4) NOTE: PROVIDE GFI PROTECTION FOR TEMPORARY CONSTRUCTION RECEPTACLES |