Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/05/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 2. USE APPROVED MANUFACTURES HARDWARE FOR OUTLET NOT DRYWALL SCREWS 3. CORD NOT ALLOWED ABOVE CEILING 400.7 & 8 INSTALL AS PER MANUFACTURES INSTRUCTION |
|
| 12/15/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 12/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* STRAPPING TO BE SECURELY ATTACHED OK WALLS |