Inspection History: ELECTRIC - PROGRESS

Permit Number - T06CM06222

Inspection Description - ELECTRIC - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
02/16/2007 ELECTRIC - PROGRESS Approved IVRS - Inspection :*
02/12/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
OK WALLS ROOM 1061 A & B
02/05/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
01/31/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
01/23/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
01/17/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
01/11/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1. A BARRIER MAY BE NEEDED IF DEVICES (BETWEEN) ARE MORE THAN 300 V

OK WALLS ROOM 1115
01/10/2007 ELECTRIC - PROGRESS Partial Approval IVRS - Inspection :*
1. PREVENT DIE ELECTRIC CONTACT
2. PROTECT M/C CABLES & FLEX AT CROSS BRACES
3. SUPPORT M/C CABLES 12" OF BOXES
4. PLEASE VERIFY USAGE OVER 250V PER 250.97

OK WALLS ROOMS 1125, 1151