Permit: T06CM06222

Parcel: 12709001E

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM06222

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/16/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
02/05/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK PHASE III TCO
01/31/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6
2. FILL UNUSED OPENINGS IN BOX NOT OLD FITTINGS.

OK JUNCTION BOX
01/23/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK PHASE 1 & 2 TCO
01/17/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. ATTACH SUPPORT WIRES AT BOTH ENDS 300.11
2. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 3

OK TO TILE EXCEPT AS NOTED

*NOTE: BOXES MORE THAN 1/4" FROM BOX TO SURFACE TO USE AN APPROVED EXTENDER RING - 314.20