Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM06222
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/16/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
02/05/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK PHASE III TCO |
|
01/31/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. VDV CABELING TO BE AS PER 725.3 & 6, 800.3 & 6 2. FILL UNUSED OPENINGS IN BOX NOT OLD FITTINGS. OK JUNCTION BOX |
|
01/23/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK PHASE 1 & 2 TCO |
|