Permit: T06CM06216

Parcel: 14042072A


Addresses:

7060 S TUCSON BL


Inspection Status: Approved

Inspection History: MECHANICAL - HOOD SYSTEMS

Permit Number - T06CM06216

Inspection Description - MECHANICAL - HOOD SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2007 MECHANICAL - HOOD SYSTEMS Approved IVRS - Inspection :*
02/28/2007 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
CHECKED ACCESS DOORS
OK FOR CEILING TILES
02/27/2007 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
CHECKED FIRE WRAP ON ROOFTOP DUCT.
OK TO ENCLOSE ROOF CURB.
DISCUSSED ACCESS DOORS.
02/26/2007 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
CLEANOUT DOORS NOT DONE CORRECTLY
PROVIDE CLEANOUTS AT 3RD FLOOR
ROOFTOP OK TO COMPLETE
02/23/2007 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
USE PINS + SPEED CLIPS ON SECTIONS THAT CANNOT BE BANDED. OK TO FIRE WRAP UPPER SECTION ON ROOF.
02/22/2007 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
FINISH FIRE WRAP & CLEANOUTS
02/20/2007 MECHANICAL - HOOD SYSTEMS Not ready for Inspection IVRS - Inspection :*
02/09/2007 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
OK TO COVER HOLES IN WALLS -- ALL FLOORS
02/05/2007 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
1) OK TO INSTALL GREASE DUCTS AND HOOD
02/02/2007 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
1) CHECKED WELDS ON UPPER 45 DEGREE ELBOW-OK TO PROCEED
01/30/2007 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
MECHANICAL HOOD SYSTEM, PARTIAL APPROVED
AND INSPECTION FOR WELD ON GREASE DUCT OK
PLUS APPROVED FIRE WRAP UNDER CONDITION OF PROVIDE
SPECIFICATIONS FOR FIRE WRAP MANUFACTURER.
01/22/2007 MECHANICAL - HOOD SYSTEMS Partial Approval CHECKED WELDS ON GREASE DUCTS.
OK TO INSTALL.
OK TO START FIRE WRAP