Permit: T06CM06206

Parcel: 13313005F

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM06206

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/09/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
USE TEF TAPE ON EXTERIOR CLEANOUTS
07/26/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- NEED TO TERMINATE CLEANOUTS W/APPROVED ADAPTORS AND PLUGS AT GRADE LEVEL.
- C O IN CONCRETE REQUIRES FRANK PATTERN COVER
- ALL CO PLUGS SHALL BE WATER & GAS TIGHT
- THIS PERMIT IS FOR EXTERIOR UTILITIES ONLY
- GAS, WATER, WASTE AND VENT PIPING INSIDE BUILDING REQUIRES PERMITS ALSO.
- PVC AND PE PIPING ARE NOT APPROVED UNDER BUILDING
- YOUR PLAN FOR THIS WORK HAS NOT BEEN APPROVED
- THE WORK IS NOT INSTALLED PER YOUR PLAN
- PIPING UNDER BUILDING IS NOT PROPERLY SUPPORTED.
01/18/2007 PLUMBING - FINAL Not ready for Inspection NEED TO SEE SEWER CLEANOUTS TERMINATED, MAKE WATER AND GAS TIGHT.
ALSO, NEED TO SEE STATE APPROVAL OF INTERIOR GAS PIPING OR NEED TO INSPECT INTERIOR GAS PIPING W/TEST FOR UTILITY CLEARANCE.
01/16/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*