Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/15/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 08/10/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/08/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ALL ITEMS AS CALLED OUT FROM LAST INSPECTION 2) KITCHEN CIRCUITS NEED TO BE 20 AMP 3) PROVIDE A SEDIMENT TRAP AT WATER HEATER 4) PROVIDE AN APPROVED B-VENT CAP AT WATER HEATER B-VENT 5) STOPPED INSPECTION-NOT READY |
|
| 07/31/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VACUUM BREAKERS MISSING AT HOSE BIBS 2) IDENTIFY ALL BREAKERS IN ELECTRIC PANEL 3) BATTERY SMOKE ALARMS REQUIRED IN EACH BEDROOM 4) AIR PRESSURE TEST REQUIRED ON GAS LINE 5) 1" CLEARANCE REQUIRED FROM WATER HEATER B-VENT AND COMBUSTIBLE 6) PROTECT ELECTRIC WIRES IN WATER ROOM 7) PTR LINE AT WATER HEATER MUST BE COPPER OR IRON AND RUN TO OUTSIDE WITH POSITIVE FLOW AND DISCHARGE 6" MINIMUM AND 24" MAXIMUM FROM GROUND |