Permit: T06CM06203

Parcel: 137071010


Addresses:

5202 S 11TH AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/15/2007 BUILDING - FINAL Approved IVRS - Inspection :*
08/10/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
08/08/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ALL ITEMS AS CALLED OUT FROM LAST INSPECTION
2) KITCHEN CIRCUITS NEED TO BE 20 AMP
3) PROVIDE A SEDIMENT TRAP AT WATER HEATER
4) PROVIDE AN APPROVED B-VENT CAP AT WATER HEATER B-VENT
5) STOPPED INSPECTION-NOT READY
07/31/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VACUUM BREAKERS MISSING AT HOSE BIBS
2) IDENTIFY ALL BREAKERS IN ELECTRIC PANEL
3) BATTERY SMOKE ALARMS REQUIRED IN EACH BEDROOM
4) AIR PRESSURE TEST REQUIRED ON GAS LINE
5) 1" CLEARANCE REQUIRED FROM WATER HEATER B-VENT AND COMBUSTIBLE
6) PROTECT ELECTRIC WIRES IN WATER ROOM
7) PTR LINE AT WATER HEATER MUST BE COPPER OR IRON AND RUN TO OUTSIDE WITH POSITIVE FLOW AND DISCHARGE 6" MINIMUM AND 24" MAXIMUM FROM GROUND