Permit: T06CM06199

Parcel: 13323087J


Addresses:

7499 E BROADWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06199

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/20/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/05/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
CONTR. NOT ON SITE
RECALL INSPECTION & LEAVE MESSAGE OR MEET INSPECTOR ON SITE WITH PLANS & PERMIT, A REINSP. FEE WILL BE ASSESSED NEXT INSPECTION IF NO COMPLIANCE
02/26/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
NO ONE ON SITE
11/19/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NO WORK PROGRESS
2) NO ONE ON SITE
11/02/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED ELECTRICIAN PRESENT TO OPEN EQUIPMENT- AREAS OCCUPIED WITHOUT INSPECTIONS - PLEASE VACATE AREAS TO INSPECT
2. OPEN WALL/PARTITIONS AS DISCUSSED
3. PANEL SCHEDULE TO BE AS PER 408.4 - LEGIBLE & DISTINGUISHABLE NO ABBREVIATIONS
4. OPEN CEILING TO INSPECT
08/10/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Still no progress on previous items
Refee is unpaid
No further inspections until compliance with previous
08/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
03/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WORK COVERED WITHOUT INSPECTIONS
2. PLANS DO NOT REFLECT WORK INSTALLED.
PLEASE REVISE PLANS AND HAVE NEW CITY STAMP.