Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T06CM06186
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 02/27/2007 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | IVRS - Inspection :* 1. OK 2" UNDERGROUND PVC FROM TEMP SERVICE TO TRAILER |
|
| 02/21/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS TO BE MINIMUM 6' APART 2. INSTALL FEEDERS OR FEEDER RACEWAY |
|
| 02/06/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL ADDRESS ON SERVICE 2) WHY 2 SERVICES ? 3) NEED INHIBITOR ON ALUMINUM TERMINATIONS 4) BOND SERVICE RISERS/REMOVE PAINT UNDER HUBS 5) DRIVE GROUND RODS 8'/FLUSH 6) PROPERLY CONNECT GROUNDING ELECTRODE CONDUCTORS TO ACORNS AND TIGHTEN 7) SER CABLE NOT LISTED FOR DIRECT BURRIAL AND UNDER SIZED 8) MAINTAIN PROPER MINIMUM BURRIAL DEPTH FOR SERVICE CONDUCTORS 9) NO FEED TO TRAILER AT THIS TIME ? |