Permit: T06CM06185

Parcel: 11307142B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM06185

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/17/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ON ROOFTOP
1. INSTALL PROPER SIZE FUSES
2. MAINTAIN PROPER WORKING CLEARANCES IN FRONT OF DISCONNECTS.
3. IDENTIFY ALL DISCONNECTS/UNITS

INSIDE
1. EMERGENCY LIGHTING NOT PER PLAN
2. CHECK PANEL DIRECTORIES, INSTALL PANEL COVERS
3. STRAP WATER HEATER FLEX
4. CHECK GUTTER FILL, MAKE UP, GROUNDING, COVER
5. REFEE TO BE PAID BEFORE FINAL WILL BE APPROVED
04/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WORK IS STILL NOT READY FOR INSPECTION.
YOU WILL NEED TO PAY REINSPECTION FEE BEFORE FINAL.
04/09/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/26/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*