Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM06185
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
04/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* ON ROOFTOP 1. INSTALL PROPER SIZE FUSES 2. MAINTAIN PROPER WORKING CLEARANCES IN FRONT OF DISCONNECTS. 3. IDENTIFY ALL DISCONNECTS/UNITS INSIDE 1. EMERGENCY LIGHTING NOT PER PLAN 2. CHECK PANEL DIRECTORIES, INSTALL PANEL COVERS 3. STRAP WATER HEATER FLEX 4. CHECK GUTTER FILL, MAKE UP, GROUNDING, COVER 5. REFEE TO BE PAID BEFORE FINAL WILL BE APPROVED |
|
04/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WORK IS STILL NOT READY FOR INSPECTION. YOU WILL NEED TO PAY REINSPECTION FEE BEFORE FINAL. |
|
04/09/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
03/26/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |