Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM06185
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
04/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PREVIOUS INSPECTION ITEMS CORRECTED FOR SERVICE |
|
04/04/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* SERVICE INSPECTION 1. BONDING CONDUCTORS FOR CT CAN & SERVICE RACEWAYS STILL UNDERSIZED -- NEC 250.102C 2. SEALING LOCKNUTS NOT SEALING HOLES - INSTALL ON OUTSIDE 3. PROVIDE PRIOR INSPECTION REPORT REFEE IF NOT CORRECT NEXT INSPECTION |
|
04/03/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* SERVICE INSPECTION 1. IDENTIFY SERVICE DISCONNECT - NEC 230.70B 2. BONDING CONDUCTOR FOR SERVICE RACEWAYS, CT CAN UNDERSIZED - NEC 250.102C 3. DIFFERENT SIZED CONDUCTORS NOT ALLOWED UNDER SAME LUG - NEC 110.3 4. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - NEC 250.6 5. USE SEALING LOCKNUTS ABOVE LIVE PARTS - NEC 110 6. A BUSHING IS REQUIRED FOR CONDUCTORS #4 AND LARGER NEC 300.4F |
|
02/28/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | ||
02/27/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* LOCKED 1:15 PM |
|
02/14/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
01/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. DISPLAY ROOMS FRONT 1/2 NEW WALL OK TO COVER 2. STOCK RM & BATHROOMS NOT READY |
|
01/22/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES NOT PROPERLY MOUNTED - NEED BRACKET TYPE 4SQ BOX OR EXTERNAL BRACE -- NEC 314.23 B1 2. NEED PLANS ON SITE, WIRING IN WALLS APPEARS TO BE INCOMPLETE. |