Permit: T06CM06185

Parcel: 11307142B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM06185

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/23/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PREVIOUS INSPECTION ITEMS CORRECTED FOR SERVICE
04/04/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
SERVICE INSPECTION
1. BONDING CONDUCTORS FOR CT CAN & SERVICE RACEWAYS STILL UNDERSIZED -- NEC 250.102C
2. SEALING LOCKNUTS NOT SEALING HOLES - INSTALL ON OUTSIDE
3. PROVIDE PRIOR INSPECTION REPORT

REFEE IF NOT CORRECT NEXT INSPECTION
04/03/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
SERVICE INSPECTION

1. IDENTIFY SERVICE DISCONNECT - NEC 230.70B
2. BONDING CONDUCTOR FOR SERVICE RACEWAYS, CT CAN UNDERSIZED - NEC 250.102C
3. DIFFERENT SIZED CONDUCTORS NOT ALLOWED UNDER SAME LUG - NEC 110.3
4. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - NEC 250.6
5. USE SEALING LOCKNUTS ABOVE LIVE PARTS - NEC 110
6. A BUSHING IS REQUIRED FOR CONDUCTORS #4 AND LARGER NEC 300.4F
02/28/2007 ELECTRIC - INTERMEDIATE Partial Approval
02/27/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
LOCKED 1:15 PM
02/14/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. DISPLAY ROOMS FRONT 1/2 NEW WALL
OK TO COVER
2. STOCK RM & BATHROOMS NOT READY
01/22/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES NOT PROPERLY MOUNTED - NEED BRACKET TYPE 4SQ BOX OR EXTERNAL BRACE -- NEC 314.23 B1
2. NEED PLANS ON SITE, WIRING IN WALLS APPEARS TO BE INCOMPLETE.