Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T06CM06162
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/15/2010 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
02/23/2010 | MECHANICAL - ABOVE CEILING | Denied | 1) ROOM 133 R/A NOT INSTALLED 2) FLEX NOT CONNECTED IN WEST CORRIDOR 3) UNIT AT S.W. CORNER ACCESS BLOCKED BY FRIDWIRE 4) UNITS NEED TO BE LABELED 5) RM 129 DUCTS IN ATTIC NOT CONNECTED INSPECTION STOPPED AT THIS TIME TOO MANY INCOMPLETE ITEMS. |
|
02/22/2010 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PROVIDE ACCESS TO DAMPERS 2) OK TO ROCK LIDS IN RESTROOMS |
|
01/08/2009 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* |