Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM06153
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/14/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/04/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MCC NOT MARKED AS SUITABLE FOR SERVICE EQUIPMENT NEC 230.66 2. STRAP LIQUID TIGHT PER NEC 350.30 3. GROUNDED CONDUCTORS TO BE BROUGHT TO SERVICE EQUIPMENT - NEC 250.24 4. BOND CT CABINET & RACEWAYS PER NEC 250.92, 250.102, 250.66, 250.97 5. GROUND LUGS NOT MARKED FOR 2 WIRE TERMINATION 6. MARK SERVICE DISCONNECTS - NEC 230.70 7. GROUNDS NOT SIZED PER PLAN 8. PLEASE HAVE ELECTRICAL CONTRACTOR MEET INSPECTOR FOR NEXT INSPECTION |
|
02/29/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* WILL RECALL FOR MONDAY |