Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T06CM06153
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2007 | ELECTRIC - UFER | Approved | IVRS - Inspection :* OK CADWELD TO REBAR IN SLAB & FOOTINGS |
|
10/31/2007 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE PROVIDE REVISION TO PLAN SHOWING NEW LOCATION OF ALL EQUIPMENT. THIS REVISION NEEDS TO BE APPROVED BY PLANS EXAMINER 2. SOFT CORE IS NOT LISTED OR RECOGNIZED WIRING METHOD & CANNOT BE USED FOR SECONDARY FEED TO MCC 3. NEED REVISION TO PLAN SHOWING GROUNDING DETAIL AS INSTALLED. |