Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM06149
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 2002 NEC 516 3-B-4 ALL OPENINGS WITHIN 3' IN ALL DIRECTIONS TO BE WIRED AS PER CLASS I DIV 2 AREAS TO REMOVE ANY ELECTRICAL EQUIPMENT FROM AREA INCLUDING BUILDING LIGHTS ABOVE BOOTH DOORS. 2. 2002 NEC 516-4-C PANELS USED TO ISOLATE INSIDE OF BOOTH AND FIXTURE TO BE VERIFIED APPROVED FOR AREA USE (SEPARATION FROM CLASS 1 TO OUTSIDE) TAMPERPROOF AS WELL - CANNOT FIND ANY INFORMATION ON PANEL ITSELF. 3. THE LIGHT FIXTURE IS TO COMPLY WITH 2002 NEC 516.4 C3 WHICH REQUIRES IT TO BE IDENTIFIED FOR THIS LOCATION USE. 4. FINISH WIRING - WHICH IS BEING CHANGED NOW 5. HAVE PLANS ON SITE TO COMPLETE INSPECTION VERIFICATION OF ITEMS 2 & 3 MAY BE IN PAPER FORM FROM PROVIDER OF BOOTH OR ELECTRICAL ENGINEER. |
|
06/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CALLED APPLICANT "KEVIN" FOR INFO - STATED THAT HE KNOWS NOTHING OF THIS PROJECT - PROVIDE PROPER INFO ON PERMIT FOR CONTRACTOR OF RECORD. 2. ELECTRICAL INSPECTOR NEEDS TO CONSULT WITH BLD. OFFICIAL C.O.T PRIOR TO CONTINUE OF INSPECTIONS. RECALL INSPECTION OR LEAVE A PH# OF CONTACT PERSON NOTES: VERIFY NOTE #2, #3, #4 |
|
04/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NON-CLASSIFIED RATED EQUIP. (RECEPTS & COVER) INSIDE SPRAY BOOTHS - CLASSIFIED PER 516.3A #1 2. NON-CLASSIFIED WIRING METHODS WITHIN 3' AREA OF DOOR OPENINGS PER 516.3B PART 4. 3. ILLUMINATION TO COMPLY WITH 516.4 C #3, INSTALLED 2X4 GRID FIXTURES, VERIFY LISTED FOR SIDE MTD TO BOOTH SIDES USING SHEETMETAL BRACKETS. 501.5 A4 4. NO SEAL OFFS OR CLASSIFIED WIRING METHODS FOR PENETRATING CLASSIFIED TO NON-CLASSIFIED AREAS. 5. COULD NOT LOCATE CONTROL PANELS SHOWN ON PLAN 6. INTERLOCKING OF EQUIP. PER 516.10 NOT VERIFIED 7. PROVIDE LADDER FOR BOOTH TOP INSP. |
|
03/28/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. LABEL PANEL SCHEDULE WITH UPDATED CIRCUITING 2. LABEL CONTACTORS DISC. SWITCHES 3. PROVIDE REPORT PER LISTING AGENCY |
|
01/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PAINT BOOTHS WILL NEED TO BE LISTED BY UL OR OTHER APPROVED AGENCY. IF BOOTHS ARE TO BE CERTIFIED BY ENGINEER OF RECORD, USE ACIL STANDARD AS GUIDELINE. 2. HAVE CONTR. ON SITE TO ANSWER ANY QUESTIONS, COULD NOT LOCATE NEW PANEL. "HL-3" PAINT BOOTHS MUST BE LISTED AS A WHOLE - NOT JUST INDIVIDUAL COMPONENTS PER 110 NEC |