Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM06138
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/24/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NAIL PROTECT ALL WIRES AND PIPES WITHIN 1 1/4" OF THE FACE OF STUDS AND PLATES 2) FIREBLOCK ALL FURRED WALLS AT TOP PLATES AND ALL SOFFITS AND DROP CEILINGS 3) DRYER VENT PIPE MUST HAVE A SWEEP 90 DEGREE AT BOTTOM-NOT A DEAD ENDED T 4) FINISH FIREPLACE FRAME INSTALLATION, EXTERIOR COMBUSTION AIR, FIREBLOCKING AT CEILING AND INSTALL 3 STRAPS AT FLUE TURN |
|
01/10/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |