Permit: T06CM06131

Parcel: 107142270


Addresses:

2435 N CASTRO AV

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
02/22/2008 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
02/01/2008 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) OK GROUND RODS
2) OK WATER BOND
3) PREVIOUS INSPECTION ITEMS CORRECTED
4) REVISION FOR CHANGES TO BE APPROVED
01/31/2008 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WATER PIPE BOND TO BE 2/0
2. BOND SPRINKLER PIPE
3. BOND TO GUTTER TO BE 2/0
4. PROVIDE LETTER FROM ENGINEER FOR CONDUCTOR CHANGES
5. PLANS CALLS FOR ADDITIONAL 2 GROUND RODS
6. MARK "SERVICE DISCONNECTS"
7. PREVENT OBJECTIONABLE CURRENT ON BONDING/GROUNDING CONDUCTORS