Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 02/01/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) OK GROUND RODS 2) OK WATER BOND 3) PREVIOUS INSPECTION ITEMS CORRECTED 4) REVISION FOR CHANGES TO BE APPROVED |
|
| 01/31/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WATER PIPE BOND TO BE 2/0 2. BOND SPRINKLER PIPE 3. BOND TO GUTTER TO BE 2/0 4. PROVIDE LETTER FROM ENGINEER FOR CONDUCTOR CHANGES 5. PLANS CALLS FOR ADDITIONAL 2 GROUND RODS 6. MARK "SERVICE DISCONNECTS" 7. PREVENT OBJECTIONABLE CURRENT ON BONDING/GROUNDING CONDUCTORS |