Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 12/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK REMAINDER OF WALLS AND HARD LIDS *NOTE: TEMPORARY TRAILER LIGHTING TO BE WIRED PER CODE OR DEENERGIZED AND REMOVED ASAP TEST SWITCHES/LIGHTS FOR E-CANS MUST BE MOUNTED IN CEILING (VISIBLE) FOR FINAL |
|
| 11/29/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER 3/A TO EAST, ENTIRE LENGTH |
|
| 09/10/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR CONSTRUCTION TRAILER 1. IDENTIFY SERVICE PANEL DIRECTORY - NEC 408.4 2. EQUIPMENT GROUNDING CONDUCTORS #6 & SMALLEER TO BE GREEN OR BARE ENTIRE LENGTH - NEC 250.119 3. NEUTRAL NOT ALLOWED TO MAKE CONNECTION TO GROUND ON LOAD SIDE OF SERVICE DISCONNECT - NEC 250.24 A-5, 250.32 B1 4. NEED TO GROUND TRAILER STEEL - NEC 550.2, 550.16 AFTER YOU HAVE MADE ALL CORRECTIONS, ENERGIZE TRAILER AND MAKE SURE ALL IS SAFE AND WORKING PROPERLY NOTE: ELECTRICIAN SHOWED UP & MADE CORRECTIONS |