Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/05/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 01/18/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* AFTER SCH. INSP. CHK. NO.1200 AMT. $108.00 REC'D 1-17-07 1. RAMPS NOT IN COMPLIANCE WITH 405.2 ANSI CODE MAXIMUM 8% = 1:12 2. RESTROOMS SIGNAGE OK 3. GRAB BARS FOR WATER CLOSET NOT IN COMPLIANCE PROVIDE VERTICAL GRAB BAR 18" REAR GRAB BAR 36" MIN. DRAWINGS FOR CORRECT GRAB BARS LEFT 1/17/07 4. RESTROOM NOT IN COMPLIANCE WITH CORRECT CLEARANCES. CONTACT NAME: MARILYN WARRIOR CONST. 351-9679 ON SITE 3:30 PM 1/17/07 |
|
| 12/21/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 12" ADDRESS DISPLAY REQUIRED PER PCZO 2. 3" SUITE # REQUIRED 3. SPLIT FRONT TOILET SEATS REQUIRED 4. MAX HEIGHT OF ACCESSIBLE LAVATORY IS 34" 5. GRAB BARS PER ANSI 117.1 REQUIRED 6. PLAN SHOWS INCORRECT BATHROOM AS ACCESSIBLE 7. SIGNAGE PER CHAPTER 11 IBC MISSING 8. LEVER HANDLE HARDWARE REQUIRED ON ACCESSIBLE DOORS. 9. THRESHOLDS ON ACCESSIBLE ROUTES TO MEET CHAPTER 11 IBC REQUIREMENTS. |