Permit: T06CM06118

Parcel: 129041830

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T06CM06118

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/05/2007 BUILDING - FINAL Approved IVRS - Inspection :*
01/18/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
AFTER SCH. INSP. CHK. NO.1200 AMT. $108.00
REC'D 1-17-07

1. RAMPS NOT IN COMPLIANCE WITH 405.2 ANSI CODE
MAXIMUM 8% = 1:12
2. RESTROOMS SIGNAGE OK
3. GRAB BARS FOR WATER CLOSET NOT IN COMPLIANCE
PROVIDE VERTICAL GRAB BAR 18" REAR GRAB BAR 36" MIN.
DRAWINGS FOR CORRECT GRAB BARS LEFT 1/17/07
4. RESTROOM NOT IN COMPLIANCE WITH CORRECT CLEARANCES.

CONTACT NAME: MARILYN
WARRIOR CONST. 351-9679
ON SITE 3:30 PM 1/17/07
12/21/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 12" ADDRESS DISPLAY REQUIRED PER PCZO
2. 3" SUITE # REQUIRED
3. SPLIT FRONT TOILET SEATS REQUIRED
4. MAX HEIGHT OF ACCESSIBLE LAVATORY IS 34"
5. GRAB BARS PER ANSI 117.1 REQUIRED
6. PLAN SHOWS INCORRECT BATHROOM AS ACCESSIBLE
7. SIGNAGE PER CHAPTER 11 IBC MISSING
8. LEVER HANDLE HARDWARE REQUIRED ON ACCESSIBLE DOORS.
9. THRESHOLDS ON ACCESSIBLE ROUTES TO MEET
CHAPTER 11 IBC REQUIREMENTS.