Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/22/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAXIMUM ALLOWED FUSES FOR AC 40 AMP 50-60 AMP FUSES INSTALLED (REPEAT) 2) ALL KITCHEN COUNTER OUTLETS MUST BE GFCI PROTECTED REPORT |
|
| 05/21/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LAG BOLTS ON BALCONY GUARDRAIL LOOSE 2) OUTLET ABOVE DISHWASHERON DBL SWITCH SHOULD BE GFI 3) DRAWINGS CALL FOR REULAR OUTLET 4) THE DRAWINGS ARE WRONG. CODE CALLS FOR ALL OUTLETS IN KITCHEN COUNTER TO BE ON GFI LOOP 5) A/C UNIT CALL FOR MAX 40 AMP FUSES |
|
| 05/18/2007 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER SUPER |
|
| 05/17/2007 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NO ACCESS 2) USE NOLOX OR EQUIVALANT ON ALUMINUM WIRES |