Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/06/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* STILL NEED PROPER CRIMP TOOL OK DRYWALL ADDITION |
|
| 04/23/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED RECEPTACLE WITHIN 6' OF BROKEN WALL LINE AND NO MORE THAN 12' RECEPTACLE TO RECEPTACLE 2. NEED RECEPTACLE IN HALL 3. USE PROPER CRIMP TOOL OR WIRE NUT FOR CRIMP SLEEVES AND TWIST WIRES 4. INSTALL NAIL PLATES AS NEEDED |