Permit: T06CM06092

Parcel: 12504083C


Addresses:

1058 N CAMPBELL AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CONDUCTORS IN PANEL NEED TO BE PERFORMED BACK AWAY FROM COVER.
2. SERVICE ENTRANCE CONDUCTORS ARE 1/0 COPPER
NOT 3/0 COPPER AS SHOWN ON PLAN.
3. PLAN SHOWS A 200 AMP FEED NOT A 150 AMP FEED
4. MORE CIRCUITRY HAS BEEN ADDED - PLANS SHOW 138.5 AMPS ON C LEG BUT MORE CIRCUITS ADDED.