Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDUCTORS IN PANEL NEED TO BE PERFORMED BACK AWAY FROM COVER. 2. SERVICE ENTRANCE CONDUCTORS ARE 1/0 COPPER NOT 3/0 COPPER AS SHOWN ON PLAN. 3. PLAN SHOWS A 200 AMP FEED NOT A 150 AMP FEED 4. MORE CIRCUITRY HAS BEEN ADDED - PLANS SHOW 138.5 AMPS ON C LEG BUT MORE CIRCUITS ADDED. |