Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/31/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUPPORT CABLES ABOVE PANEL & BELOW PER CODE 12" 2. CHECK BOX FILL OK WALLS |
|
| 01/29/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. HAVE INCOMPLETE WIRING IN WALLS, INCOMPLETE RACEWAYS. 2. DE-ENERGIZE/REMOVE ALL OLD CKTS IN WALLS OR AREAS THAT WILL BE COVERED. 3. IN BOXES - WRAP EQUIPMENT GROUND ALL THE WAY AROUND GROUND SCREWS, BUT DON'T OVERLAP CONDUCTOR AROUND SCREW, TIGHTEN GROUND SCREWS. 4. PROVIDE NAIL PLATES FOR MC AS NEEDED 5. FINISH UNDERGROUND RACEWAYS GOING INTO WALL 6. INSTALL MUD RINGS 7. WIRING BETWEEN SPACES INTERMINGLED DO NOT CALL BEFORE READY OR REINSPECTION FEE WILL BE CHARGED. |
|
| 01/04/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER UNDERGROUND RACEWAY FOR ICE CREAM COUNTER RECEPTACLES CKTS #13 & 11 |