Permit: T06CM06091

Parcel: 11107271F

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
03/16/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
WATER TEST UNDERGROUND ONLY THRU BUILDING PER PLAN TO 4' PAST 2-WAY OK
NOTE: 4" BUILDING DRAIN SHALL TIE INTO 4" SEWER AT HCS CONNECTION PLEASE VERIFHY THIS CAN HAPPED WITH CORRECT FALL 1/4" PER FOOT.
2. 1 1/4 PVC SCH 40 FROM METER LOCATION TO STUB-UPS AT EAST SIDE FOR EACH UNIT. REDLINE TO BE ON SITE AS REQUESTED 3/15/07
03/15/2007 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
LOCK CODE 1420

1. CORRECT SLOPE AND CHECK FOR LEAKS
2. UNCOVER FITTINGS AND PIPING, TOP OFF WATER TEST
3. YARD WATER OK TO COVER, REDLINE PLANS AND REVISE PLAN FOR CHANGE OF WATER SERVICE.