Permit: T06CM06091

Parcel: 11107271F

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
OK FINAL
07/25/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR SOUTH UNIT ONLY
CHECK BOTH UNITS

1. INSTALL RANGE ANTI-TIP DEVICES - NEC 110.3B
2. MAXIMUM LENGTH DISPOSAL CORD 36" - NEC 422.16B
3. DISCONNECT FOR WATER HEATERS TO BE NO HIGHER
THAN 6'7" FROM FLOOR. SEE NEC 404.8 ALSO, SEE NEC 422.31B
4. STRAP FLEX OUT OF AC DISCONNECTS WITHIN 12" -
NEC 350.30A
5. PROVIDE SEPARATE ROOFTOP RECEPTACLE FOR EACH UNIT POWERED BY THAT UNIT -- NEC 210.63
6. REMOVE NEUTRAL BOND FOR RANGE TAIL -
NEC 110.3B, NEC 250.140