Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T06CM06088

Parcel: 140552450

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/29/2007 FRAMING Approved IVRS - Inspection :*
02/05/2007 FRAMING Partial Approval IVRS - Inspection :*
1) PENDING STAMPED BY CITY ENGINEERING FOR CUT FLOOR TRUSSES
2) REVISE PLAN FOR NEW (DIFFERENT) HANGERS
01/26/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PLANS CALL FOR SIMPSON HANGERS FOR TRUSSES PER S/DR
USP TF/418 HANGER USED.
HAVE PLAN REVISED TO SPECIFY WHICH HANGERS TO USE.
HAVE HANGER SUPPLIER COMPLETE CATALOG/INSTALLATION INSTRUCTIONS ON SITE FOR NEXT INSPECTION.
2. HAVE TRUSS REPAIR DOCUMENT APPROVED BY CITY OF TUCSON FOR THIS ADDRESS.
3. TWO INCH CLEARANCE REQUIRED BETWEEN WEEP SCREED AND CONCRETE.
4. OK TO INSULATE AND DRYWALL ALL BUT HANGERS FOR 5 TRUSSES BEARING AT 3X14 GLUE LAM BEAM.
01/24/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 2" CLEARANCE REQUIRED BETWEEN STUCCO WEEP SCREED IN REAR PORCH CONCRETE
2) STUCCO LATH NOT STAPLED UNDER PORCH LEDGER
3) PROVIDE SHEAR CONNECTION AT GARAGE SHEARWALL 2
4) NO POWER ROOM EXHAUST FAN
5) PLAN CALLS FOR KITCHEN TO VENT TO ROOF
6) A/C SECONDARY CONDENSATE MUST DRAIN IN CONSPICOUS LOCATION OVER WINDOW OR DOOR
7) NO ATTIC VENTS SEE NOTE 1 A-2
8) 5 TRUSSES CUT AND 5 TRUSSES TO SHORT. PROVIDE CITY OF TUCSON APPROVED ENGINEERING REPAIR BY ADDRESS. TRUSSES ARE LIVING ROOM G.L.B.
9) STOPPED INSPECTION