Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM06082
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXTERIOR EAST AND WEST EMERGENCY LIGHTS NOT WORKING 2. WHERE LIGHTING CIRCUIT IS UPSIZED TO #10, NEED #10 GROUND - NEC 250.122 B 3. SEAL SPARE RACEWAY OUT OF PANEL - NEC 110.12A 4. HAVE OVERFILLED J-BOXES -- NEC 314.16 5. STUB FUTURE RACEWAYS OUT OF WALL. INSTALL KO SEAL 6. GROUND TIME CLOCK & CONTACTOR ENCLOSURES - NEC 250.148 |