Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM06082
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/10/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/09/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/26/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* IDENTIFY SERVICE DISCONNECTS AS SUCH |
|
07/18/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR SERVICE AND SUB-PANEL ONLY 1. IDENTIFY SERVICE DISCONNECTS - NEC 230.70B 2. PLAN SHOWS #750 SERVICE LATERAL CONDUCTORS NOT #500 (PARALLEL) 3. PLAN DOES NOT SHOW WIRING INTO GUTTERS/CT CABINETS - REVISE AND SHOW FAULT CURRENTS 4. #6 & SMALLER NEUTRAL TO BE WHITE ENTIRE LENGTH NEC 200.6 5. 400 AMP DISCONNECT COVER MISSING SCREWS 6. SHEETMETAL SCREW NOT ALLOWED FOR MAIN BONDING JUMPER BAR IN SAME DISCONNECT -- NEC 250.8 PARTIAL INSPECTION ONLY REVISE PLANS TO SHOW ACTUAL SCOPE OF WORK AND ALL FAULT CALCULATIONS. |