Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 09/17/2007 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE TAPE ON THE FLEX DUCT DETAIL IS INTENDED TO SEAL BOTH ENDS OF THE FLEX DUCT. USE ONLY LISTED 181A OR B TAPE |
|
| 08/27/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES EVERYWHERE EXCEPT LARGE GROUP ROOM EAST SIDE OF BLDG. |
|
| 08/23/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* STRAP FLEX DUCT UP OFF GRID RELOCATE REFER LINE BLOCKING ACCESS TO FAN COIL ID FAN COILS REPLACE ALL SMASHED DUCT BETWEEN 2 FAN COILS INSTALL FLEX DUCT AS PER DETAILS ON PLANS DO NOT USE 1/2" LONG SCREWS TO SUPPORT DUCTS |
|
| 07/23/2007 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* - PROVIDE 1/8" PER FT. SLOPE ON ALL CONDENSATE DRAINS - |