Permit: T06CM06047

Parcel: 113010500

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
09/20/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/17/2007 MECHANICAL - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
THE TAPE ON THE FLEX DUCT DETAIL IS INTENDED TO SEAL BOTH ENDS OF THE FLEX DUCT. USE ONLY LISTED 181A OR B TAPE
08/27/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK CEILING TILES EVERYWHERE EXCEPT LARGE GROUP ROOM EAST SIDE OF BLDG.
08/23/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
STRAP FLEX DUCT UP OFF GRID
RELOCATE REFER LINE BLOCKING ACCESS TO FAN COIL
ID FAN COILS
REPLACE ALL SMASHED DUCT BETWEEN 2 FAN COILS
INSTALL FLEX DUCT AS PER DETAILS ON PLANS
DO NOT USE 1/2" LONG SCREWS TO SUPPORT DUCTS
07/23/2007 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
- PROVIDE 1/8" PER FT. SLOPE ON ALL CONDENSATE DRAINS
-