Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/20/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 09/17/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* LOCKED - NO ACCESS - COULD NOT UNDERSTAND PHONE # |
|
| 08/23/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK CEILING TILES EXCEPT EAST ROOM FAN COIL WIRING WILL BE INSPECTED ON FINAL |
|
| 08/13/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FINISH LOW VOLTAGE/DATA WIRING 2. SUPPORT FIXTURE WHIPS OFF GRID -- NEC 300.11 3. SEAL UNUSED/SPARE RACEWAYS - NEC 110.12A 4. GROUND ALL BOXES - NEC 250.148 5. HAVE OVERFILLED BOXES - NEC 314.16 6. HAVE OVERFILLED WIRE NUTS -- NEC 110.3B OK TO COVER PANEL "B" FEEDER @ SERVICE OK TO COVER RACEWAYS TO AC'S 7. WIRE AND IDENTIFY FAN COILS 8. SEPARATE NEUTRAL & GROUND PANEL "B" DISCONNECT 9. IDENTIFY SERVICE DISCONNECT |
|
| 07/19/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK HARD LID COVER A. PANEL ROOM B. BATHROOMS C. ENTRY CORRIDORS - FRAME ACCESS OPENING IN FRONT OF AIR HANDLER DISCONNECTS AND PROVIDE ATTIC SERVICE LIGHTING. |