Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM06040
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/23/2007 | ELECTRIC - INTERMEDIATE | Approved | PER INSP CARD | |
01/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 2. WE HAVE BOX OVERFILL 3. 20 AMP DISCONNECT NEEDED FOR BATHROOM A/C 4. ELECTRIC SUPPORT WIRES PER 300.11 |
|
12/21/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
12/20/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PLEASE PROVIDE A LETTER AUTHORIZING USAGE OF M/C CABLE 2. PROTECT M/C CABLES AT SHALLOW STUDS OK 2X4 STUD WALLS * EXISTING VDV CABELING TO BE AS PER 725.3 & 6 800.3 & 6 |