Permit: T06CM06040

Parcel: 12709011M

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/23/2007 ELECTRIC - INTERMEDIATE Approved PER INSP CARD
01/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
2. WE HAVE BOX OVERFILL
3. 20 AMP DISCONNECT NEEDED FOR BATHROOM A/C
4. ELECTRIC SUPPORT WIRES PER 300.11
12/21/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
12/20/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. PLEASE PROVIDE A LETTER AUTHORIZING USAGE OF M/C CABLE
2. PROTECT M/C CABLES AT SHALLOW STUDS

OK 2X4 STUD WALLS

* EXISTING VDV CABELING TO BE AS PER 725.3 & 6
800.3 & 6