Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM06039

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T06CM06039

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/24/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/14/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE NEOPRENE PADS UNDER CU's PER PLANS
2. PROVIDE RUBBER GROMMETS AT ALL REFRIGERATION LINES ENTERING UNITS.
3. PROVIDE I.D PLATES PER GENERAL NOTE 3.08 M2.1
4. PROVIDE OUTSIDE AIR HOODS ON ALL ROOFTOP
PACKAGE UNITS
5. PROVIDE DUCT SMOKE DETECTOR AT RTU-3 RETURN DUCT
10/07/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
SCREWS IN FIRE DAMPER TRACK NOT
ALLOWING DAMPER TO CLOSE
10/02/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE GRILLS AT ELECTRIC ROOM EXHAUST
HANGER MAIN FUME EXHAUST DUCT (3) OK