Inspection History Details
Permit: T06CM06039
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/24/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/14/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE NEOPRENE PADS UNDER CU's PER PLANS 2. PROVIDE RUBBER GROMMETS AT ALL REFRIGERATION LINES ENTERING UNITS. 3. PROVIDE I.D PLATES PER GENERAL NOTE 3.08 M2.1 4. PROVIDE OUTSIDE AIR HOODS ON ALL ROOFTOP PACKAGE UNITS 5. PROVIDE DUCT SMOKE DETECTOR AT RTU-3 RETURN DUCT |
|
| 10/07/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SCREWS IN FIRE DAMPER TRACK NOT ALLOWING DAMPER TO CLOSE |
|
| 10/02/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE GRILLS AT ELECTRIC ROOM EXHAUST HANGER MAIN FUME EXHAUST DUCT (3) OK |