08/20/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
08/18/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* HANGERS ON FLEX DUCT NOT TO EXCEED 5' SECOND FLOOR HARD LID AREAS OK FOR ROCK |
|
08/05/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1ST FLOOR OK TO ROCK MECHANICAL ONLY |
|
07/30/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SUSPENDED UNIT ON CEILING 2. DUCT NOT SEALED 3. FLEX PINCHED OFF AT UTILITY ROOM 4. NO SECONDARY DRAIN ON AIR HANDLER 5. PROVIDE 1" LINER ON LINEAR DIFFUSER BOXES |
|