Permit: T06CM06039

Inspection Status: Approved

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T06CM06039

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Approved

Date Description Inspector Results Comments
07/30/2008 ELECTRIC - TEMPORARY SERVICE Approved IVRS - Inspection :*
08/28/2007 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
OK MODULAR OFFICE
08/21/2007 ELECTRIC - TEMPORARY SERVICE Partial Approval IVRS - Inspection :*
1) NEED TO SEE CONNECTION TO MODULAR
08/20/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND RODS TO BE FLUSH WITH GRADE. NEC REQUIRES 8' IN GROUND
2) USE 1/4" BOLTS FOR RISER SUPPORT. BLUE #12 SCREWS TO WEAK-SPLIT 2 X 4 BACKING NOT SECURELY SUPPORTED
08/17/2007 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. DRYWALL SCREWS NOT APPROVED FOR RISER SUPPORT. USE 1/4 BOLTS
2. 2 GROUND RODS REQUIRED, EXPOSE 2ND ROD
3. INSTALL PERMANENT ADDRESS LABEL ON SERVICE PER NEC