Permit: T06CM06039

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
10/17/2008 ELECTRIC - INTERMEDIATE Approved
09/09/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
ONLY NEED TO SEE MILL WORK AT RECEPT. DESK TO SIGN
OFF INTER. 02035
08/14/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS EXCEPT RECEPTION PONY WALLS
2. OK HARD LIDS
08/11/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK COMPRESSOR ROOM ROUGH
2. OK ROOMS 216, 211, 209 ROUGH
08/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & HARD LIDS 1ST FLOOR
07/30/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
07/29/2008 ELECTRIC - INTERMEDIATE Cancelled IVRS - RI canceled
07/21/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK RESTROOMS WALLS & HARD LIDS AND KITCHEN AREA
2) OK WALLS IN ELECTRIC ROOM AND SERVICE OFFICE
07/15/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK CAN LTG. IN WAITING ROOM, EXTERIOR SOFFIT LTG. 2ND FLOOR
2. RECEIVED LETTER OF TORQUE & GFI MAIN TEST
3. BOND X-FORMER
4. POST BOND FOR TEMP POWER FOR TEST
07/14/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUPPORT CONDUIT PER CODE, WITHIN 3' & 10'
2. IF YOUR USING TIE WIRE, TIES MUST BE EFFECTIVE
3. SOFFIT LTG. NOT COMPLETE